Product Advantages
Efficient integration ① High system integration, integrating battery system, AC system, temperature control system, fire protection system, data monitoring system, etc.;② Integrated container-type energy storage system design is convenient for transportation, simple construction, and low installation cost. | High precision & intelligence ①Meet smart grid design specifications;② Integrate the local controller to achieve unified dispatch management, and the stand-alone system can independently perform peak shaving and valley filling; ③ Equipped with PQ, VF, SVG and other functions to support independent operation of microgrid; ④Outdoor design, protection grade IP54. | Efficient conversion ①Intelligent temperature control system to improve system efficiency and battery cycle life;② It has bidirectional current conversion, and charging has constant current, constant voltage and constant power modes. |
Specifications
Model | PLPF0280C0-0768R0A | |
Cell Parameters | ||
Cell type | 3.2V/ 280Ah | |
S/P No. | 1P240S | |
System Capacity | 215.04KWh | |
Rated voltage | 768V | |
Operating voltage | 600~876V | |
On-grid Output Parameters | ||
Rated output power | 100kW | |
Max output power | 110kVA | |
Max output current | 158A | |
AC rated voltage | 400V | |
Grid voltage range | -15~+10% | |
Rated grid frequency | 50Hz | |
Power factor | >0.99(at rate power) | |
Current harmonic total distortion rate | ≤3(at rate power) | |
DC component | <0.5%(at rated output current) | |
Off-grid Output Parameters | ||
Rated output power | 100KW | |
Max output power | 110kVA | |
Max output current | 158A | |
AC rated voltage | 400V | |
Output voltage accuracy | 1% | |
System Parameters | ||
Container dimensions (width × height × depth) | 2100X2500X1100mm | 1300X2600X1000mm |
Isolation method | transformer isolation (optional) | |
Weight | 2.65 T | |
Protection level | IP54/IP55(optional) | |
Anti-corrosion level | C4/C5(optional) | |
Operating temperature range | -30~60℃(>40℃ reduce power) | |
Humidity range | 0~95%(No condensation) | |
Cooling method | Temperature controlled forced air cooling | |
Fire fighting methods | Aerosol/heptafluoropropylene (optional) | |
Highest altitude | 4000m(>2000m reduce power) | |
Communication Protocol | Modbus-TCP/Modbus-RTU/IEC104 | |
Communication method | RS485/Ethernet |